High Voltage Outdoor Terminations upto 245 kV – Dry type and Fluid filled type with Composite insulator including link boxes. Composite terminations for voltage classes up to 245 kV operate under severe environmental conditions. Composite housings with creepage lengths up to 31 mm/kV are available for the most common and extremely pollution levels, according to IEC 60815 standard.
Fluid filled Composite Insulator Termination – leak proof and light weight composite housing
Fittings made of corrosion-resistant alloy
Prefabricated and factory-tested silicone-rubber stress cone
Torque-controlled shear head mechanical connector
Insulating-oil filling without preheating
No special tools required for installation
Insulated base plate for sheath sectionalization
Type tested according to IEC 60840 and IEC 62067 standards
Dry and Dry Flexible Self-Support Termination – Dry interface, no oil-filling
Self-supporting
Prefabricated and factory tested silicone-rubber stress cone
Torque-controlled shear head mechanical connector/compression connector
Fast and simple installation combining GIS plug-in technology with polymeric insulators
No special tools required for installation
Insulated base plate gland for sheath sectionalization
Type tested according to IEC 60840
Oil filled 72/145/245 kV
Rated Voltage kV
36/66 (72.5)
76/132 (145)
127/220 (245)
Diameter over insulation
38.87 to 96.80
38.87 – 96.80 mm
62.33 – 128.25 mm
Diameter over sheath
≤120mm
≤140 mm
≤160 mm
Cable screen type
Corrugated Al. sheath, Copper wire, Copper tape, Lead sheath.
Corrugated aluminium sheath/Lead sheath/Cu wire. etc.
Corrugated aluminium sheath/Lead sheath/Cu wire. etc.
Cable Cross section (Al/Cu)
≤1200 mm²
≤1600 mm²
≤2500 mm²
Conductor connection
Mechanical (shear head bolts)
Mechanical (shear head bolts)
Mechanical (shear head bolts)
Material of connection bolt
Aluminium/Copper
Aluminium/Copper
Aluminium/Copper
Material of insulator – outer surface
Silicone Rubber
Silicone Rubber
Silicone Rubber
Colour of insulator
Grey
Grey
Grey
Method of stress control
Geometric
Geometric
Geometric
Stress cone
Pre-moulded silicone rubber
Pre-moulded silicone rubber
Pre-moulded silicone rubber
Insulating liquid
Silicone Oil/Ester oil/Polyisobutlyene oil
Silicone Oil/Ester oil/Polyisobutlyene oil
Silicone Oil/Ester oil/Polyisobutlyene oil
Installation temperature
0 °C – +40 °C
0 to +40
0 to +40
Operation temperature
-55 °C – +55 °C
-55 °C – +55 °C
-55 °C – +55 °C
Storage temperature
0 °C – +40 °C
0 to +40
0 to +40
Dry 145kV
Diameter over insulation
34 – 74 mm
Diameter over sheath
≤99 mm
Cable screen types
Cu-wires w/o laminated foil, lead sheath, corrugated metal sheath, Cu-tape (other types and combinations on request)
Max. Cross section (Al/Cu)
1200 mm²
Conductor connection
Mechanical (shear head bolts)
Material of connection bolt
Aluminium
Material of insulator – outer surface
Silicone rubber
Profile of insulator
Alternating sheds
Colour of insulator
Grey
Method of stress control
Geometric
Stress cone
Prefabricated silicone rubber
Max. permissible dielectric stress at core screen
4 kV/mm (at core screen of cable)
Insulating liquid
none
Material of fittings
Aluminium
,
Dry Flexible 145kV
Max. Cross section (Al/Cu)
1200 mm²
Max. XLPE Insulation diameter
≤ 78 mm
Connector style
Crimping (with Aerial Lug)
Creepage distance
4590 mm
Material of body
Silicone rubber
Comply with
IEC60840
Method of stress control
Stress cone
Cable Screen type
Cu Wire/Lead sheath/CAS/Copper tape
Grounding style
Mechanical connection without solder
Colour of insulator
Grey
Oil filled 72/145/245 kV
Relevant Standard
IEC 60840
IEC 60840
IEC 62067
Rated voltage Uo/U (Um)
kV
36/66 (72.5)
76/132 (145)
127/220 (245)
Rated frequency
Hz
50
50
50
Lightening impulse voltage 1.2/50µs
kVp
350
650
1050
Power frequency voltage withstand dry (15/30 min)
kV
90
190
254/318
Partial Discharge 1.5Uo (kV)
pC
≤5
≤5
≤5
Rated Current
kA
as per cable
as per cable
as per cable
Rated Short Circuit Current (conductor) 1s
kA
as per cable
as per cable
as per cable
Rated Short Circuit Current (sheath) 1s
kA
as per cable
as per cable
as per cable
Creepage distance (min.)
mm
2250
4500
7595
Flash-over distance
mm
740
1340
2320
Pollution level (IEC 60137; 1995, VDE 0674 Teil5)
IV
IV
IV
Withstand voltage of support insulators (AC/DC)
kV
10/20
10/20
10/20
Dry 145 kV
Relevant standard
IEC 60840 / IEEE 48
Rated voltage Uo/U (Um)
kV
76/132 (145)
Rated frequency
Hz
50
Lightening impulse voltage 1.2/50µs
kV
650
Power frequency voltage withstand dry (1 min)
kV
310
Power frequency voltage withstand wet (10 s)
kV
275
DC voltage withstand (15 min)
kV
355
Rated current
kA
as per cable
Rated short-circuit current (conductor)
kA
as per cable
Rated short-circuit current (sheath) 1s
kA
as per cable
Total creepage distance
mm
4680
Protected creepage distance (90° shadow)
mm
1820
Flash-over distance
mm
1320
Withstand voltage of support insulators (AC/DC)
kV
10/20
Dry Flexible 145 kV:
Relevant standard
IEC 60840
Rated voltage Uo/U (Um)
kV
76/132 (145)
Highest voltage
Hz
50
Lightening impulse voltage
kVp
650
Power frequency voltage withstand dry (30 min)
kV
190
Current capacity
A
as per cable
Permissible short-circuit current 1s
kA
as per cable