GIS/Equipment Terminations

GIS/Equipment Terminations

The dry compact GIS/Transformer termination for voltage classes up to 245 kV is designed to be installed in cable entry housings of gas-insulated switchgear (GIS)/Transformer.

  • Make in India
  • TE
  • Complies with IEC 62271-209 standard, which essentially specifies interfaces between termination and switchgear
  • Adapters available to match dimensions of wet (oil-filled) type terminations, as specified in IEC 60859
  • Insulator can be installed by GIS / transformer manufacturer at factory, saving installation time on-site and reducing risk of contamination of cable entry housing
  • No special tools required for installation
  • Easily separable, consists of a plug-in part and epoxy resin insulator
  • Transformer Terminations comply to dimensions as per EN50299 Standard

 

Specifications

Parameter
Operates in SF6 and insulating liquids like transformer oil
Corona shield at top of Transformer termination provides shielding for terminal
Dry interfaces, no oil-filling
Pressure-tight resin housing
Prefabricated and factory-tested silicone-rubber stress cone
Torque-controlled or wedge-type multi-contact conductor bolt
Insulated cable gland for sectionalization
Type tested according to IEC 60840 and IEC 62067 standards
Design Data
Rated kV 36/69 (72.5) 76/132 (145) 127/220 (245)
Diameter over insulation range 38.40mm – 77.4 mm 38.40 mm – 95.10 mm 64.0 -123.1 mm
Diameter over sheath ≤120 mm ≤140 mm ≤160 mm
Cable screen type Corrugated Al. sheath, Copper wire, Copper tape, Lead sheath, etc. Corrugated Al. sheath, Copper wire, Copper tape, Lead sheath, etc. Corrugated aluminium sheath/Lead sheath/Cu wire. etc.
Max. Cross section (Al/Cu) ≤1200 mm² ≤1600 mm² ≤2500 mm²
Conductor connection Mechanical (shear off bolts)/Wedge connector Mechanical (shear off bolts)/Wedge connector Mechanical (shear off bolts)/Wedge connector
Material of Housing Epoxy Resin Epoxy Resin Epoxy resin
Material of connection bolt Aluminum Alloy Aluminum Alloy  Aluminum Alloy
Method of Stress Control Geometric Geometric Geometric
Type of Stress Cone Pre-moulded silicone rubber Pre-moulded silicone rubber Pre-moulded silicone rubber
Corona Shield (only for Transformer Termination) Aluminium Alloy Aluminium Alloy Aluminum Alloy
Installation temperature [°C] 0 to +40 0 to +40 0 to +40
Operation temperature -55 °C – +55 °C  -55 °C – +55 °C  -55 °C – +55 °C
Storage temperature [°C] 0 to +40 0 to +40 0 to +40

 

Technical Information

Relevant standard   IEC 60840 IEC 60840 IEC 62067
Rated voltage U0 /U (Um) kV 36/69 (72.5) 76/132 (145) 127/220 (245)
Rated frequency Hz 50 50 50
Lightening impulse voltage 1.2/50µs kV 350 650 1050
AC Voltage withstand test (15/30 min) kV 90 90  254/318
Partial discharge 1.5Uo (kV) pC  ≤5  ≤5 ≤5
Rated current kA as per cable as per cable  as per cable
Rated short circuit current conductor) 1s kA as per cable as per cable as per cable
Rated short circuit current (sheath) 1s kA as per cable as per cable as per cable
Creepage distance mm 254 410 475
Electrical Data for 72/145/245 kV GIS / Equipment Extra High Voltage Termination

Product List

#
#
#
#

Personnel Safety

If you're looking for precision, durability, and superior color

#
#
#
#

Earthing & Lightning Protection Systems

If you're looking for precision, durability, and superior color

#
#
#
#

Polymeric Surge Arresters

If you're looking for precision, durability, and superior color

#
#
#
#

Clamping

If you're looking for precision, durability, and superior color

#
#
#
#

Junction Box

If you're looking for precision, durability, and superior color

#
#
#
#

Cable Glands

If you're looking for precision, durability, and superior color

#
#
#
#

Cable Lugs & Connectors

If you're looking for precision, durability, and superior color

#
#
#
#

Power Cable Accessories

If you're looking for precision, durability, and superior color